+86-312-6775656
Sistem Pemantauan Analisis Gas Terlarut (DGA) HZGC-1210 Online Untuk Transformator Daya

Sistem Pemantauan Analisis Gas Terlarut (DGA) HZGC-1210 Online Untuk Transformator Daya

Sistem pemantauan on-line dari kromatogram oli transformator tipe HZGC-1210 dapat mewujudkan fungsi-fungsi berikut: pembersihan sirkulasi otomatis, pemisahan oli, minyak dan gas, analisis sampel, pemrosesan data, dan alarm waktu nyata; Itu bisa dengan cepat memantau konten dan pertumbuhan gas kesalahan ...
Product Details ofSistem Pemantauan Analisis Gas Terlarut (DGA) HZGC-1210 Online Untuk Transformator Daya

 

Sistem pemantauan on-line dari kromatogram oli transformator tipe HZGC-1210 dapat mewujudkan fungsi-fungsi berikut: pembersihan sirkulasi otomatis, minyak masuk, pemisahan minyak dan gas, analisis sampel, pemrosesan data, dan real{{3} }alarm waktu; Ini dapat dengan cepat memantau konten dan pertumbuhan gas gangguan yang terlarut dalam minyak minyak-trafo peralatan HV daya terendam seperti transformator. Melalui sistem pakar diagnosis kesalahan, sebelumnya dapat memperkirakan masalah tersembunyi dari kegagalan peralatan, menghindari kecelakaan peralatan, sehingga dapat mengurangi kerugian besar dan meningkatkan keandalan operasi peralatan. Sebagai produk generasi baru di bidang kromatogram minyak pada-pemantauan jalur, sistem ini akan memberikan solusi yang stabil dan andal bagi transformator daya untuk mewujudkan analisis DGA jarak jauh on-line. Oleh karena itu, merupakan jaminan yang kuat bagi terselenggaranya perombakan sistem tenaga oleh negara.

online dga system_

Sistem HZGC-1210 dirancang berdasarkan semua keunggulan pemantauan kromatogram minyak secara online di dalam dan luar negeri. Jadi sistem memiliki keunggulan yang jelas dalam aspek stabilitas, keandalan dan akurasi.

♦ On-line testing the concentration and growth rate of H2,CO,CO2,CH4,C2H4,C2H2,C2H6

♦ The method of quantitative cleaning and circulatory sampling could truly reflect the state of gas dissolved in oil.

♦ Oil-gas separation is safe and reliable without any pollution. The users could choose to discharge the transformer oil or not.

♦ It adopted dedicated composite chromatographic column to improve the degree of separation of gas component.

♦ It adopted imported detector to enhance the sensitivity of testing hydrocarbon gases.

♦ The gas detection technique has high stability and precision with ± 10 percent error range.

♦ Mature and reliable as the communication mode is, it adopted standard networking protocols and could support remote data transmission.

♦ Data collection, adopted the oversampling technology Δ - ∑ analog-digital converter with 24-bit resolution and automatic calibration, is highly reliable.

♦ Diverse data display and inquiry modes could provide report and trend chart. The storage life of historical data is 10 years.

♦ It has strong environmental adaptability, widely used in cold, hot, high humidity and high altitude areas.

♦ The performance of anti-interference is outstanding. The electromagnetic compatibility could meet GB/T17626 and IEC61000 standard.

♦ It offered 2 level of alarming set. Alerting signal could spread widely.

♦ Open database could access to LAN of electric system.

Selain itu, sistem HZGC-1210 menggunakan desain modular dengan penerapan prosesor tertanam berkinerja tinggi, membuat sistem pemantauan online kromatografi lebih stabil dan andal. Ini memiliki fitur berikut:

♦ It has faster analysis cycle which can be set by users themselves. The minimum monitoring cycle is 40 to 60 minutes. We recommend setting 24 hours as an inspection cycle;

♦ It takes only 10 minutes to separate oil and gas. It uses special environmental adaptation technology to eliminate any change of gas distribution coefficient caused by the temperature and humidity changes.

♦Analyzed oil sample adopted the technique of degassing and buffering, removing the mingled bubble in oil sample of reinjection transformer. The technique of multilayer isolated reinjection oiling (return oiling) could guarantee the carried gas would not be taken into the transformer.

♦ The minimum limit of detection of C2H2 can reach 0.1-0.5 μ L/L.

♦ It adopted double circuit and multi{{0}}mode thermostatic control with ± 0.1 degree temperature control accuracy. The device is equipped with industrial air conditioning which has the function of automatic constant temperature control.

♦ The embedded processor control system is multi-function, combining oil-gas separation, data acquisition, chromatographic analysis, concentration calculation, data alarming, and equipment condition monitoring. Cases like data loss would be avoided, greatly improving the reliability and stability of the system.

♦ Functional interface circuit adopted opto-isolator to further improve the ability of anti-interference.

♦ Via Ethernet, it could realize full-digital and remote data transmission, parameter setting and control.

♦ It improves the function of fault diagnosis, applying modified three ratio method, David trigonometry and cube graphic method to draw the diagnosis result;

♦ It strengthens self-inspection and adds the function of remote maintenance and alarming for equipment abnormality

♦ It supports 61850 communication protocol, providing networking for monitoring equipment of the same kind, so that it can realize concentrated remote diagnosis in a certain area.

♦ The system adopted 19 standard case and high-integrated modular design, which is easy to install and maintain with user-friendly operation.

♦ With wide expandability, it could integrate with other monitoring device conveniently.

♦ The design of non-cylinder saves the time and money to change the carrier gas every year so that after sale maintenance would be much easier. Without high pressure vessel nearby, transformers would be safer, free from any potential risk.

Tidak.

Nama parameter

nilai

1

Model

HZGC-1210

2

Suhu kerja

-40 degree -+70 degree

3

Kelembaban kerja

Relative humidity5-95 percent (interior of device shall be free from condensation and ice.)

4

Tekanan atmosfir

70kPa-110kPa

5

Sumber Daya listrik

AC 220 V±10 percent , 50Hz

6

Memantau konten

Pantau H2, CO, CO2, CH4, C2H4, C2H2, C2H6 dalam aspek Hidrokarbon Total, laju pertumbuhan relatif dan nilai pertumbuhan absolut. (opsional untuk memilih minyak dengan sedikit kandungan air)

7

Analisis dan diagnosis

Conduct analysis and diagnosis for the monitoring data via improved three-ratio method, Duval's triangle and cubic graphic method. Provide the original chromatography.

8

Periode deteksi minimum

Range between 40 and 60min, up to user's settings. default 24 hours

9

Metode pengambilan sampel

Pengambilan sampel sirkulasi akan mencerminkan status udara dalam transformator secara tepat.

10

Metode pemisahan minyak-gas

metode degassing vakum

11

Kehidupan penyimpanan data

Lebih dari atau sama dengan 10 tahun

12

Dilengkapi gas pembawa

generator gas

13

Gas yang dipantau

Rentang pengukuran

Nilai deteksi terendah

Kesalahan pengukuran

1)

H2

1 - 10000 µ l/l

1µ l/l

±10 percent

2)

CO, CO2

5-  50000 µ l/l

5µ l/l

±10 percent

3)

CH4

0.1 - 20000 µ l/l

0.1-0.5 µ l/l

±10 percent

4)

C2H4

0.1 - 20000µ l/l

0.1-0.5 µ l/l

±10 percent

5)

C2H6

0.1 - 20000 µ l/l

0.1 -0.5µ l/l

±10 percent

6)

C2H2

0.1 - 5000 µ l/l

0.1-0.5 µ l/l

±10 percent

7)

H2O(optional)

1 - 800 µ l/l

1µ l/l

±10 percent

8)

Jumlah hidrokarbon

1 - 8000 µ l/l

9)

Total kandungan udara

{0}{}.2 - 15 persen

14

Stability(measured deviation)

Under the same test condition, the deviation of test result shall be no more than 10 percent (medium concentration)

15

Kekebalan pelepasan elektrostatik

Grade 4,± 8kV-± 15kV

16

Imunitas transien cepat listrik

Grade 4,± 4kV

17

Kekebalan gelombang (shock)

Grade 4,± 4kV

18

Kemampuan tahan gempa: gelombang seismik adalah gelombang sinus. Waktu durasi: gelombang tiga lingkaran. Faktor keamanan: 1.67

Area dengan intensitas seismik grade 9:

Percepatan horizontal tanah {{0}}.4g, percepatan vertikal tanah 0.2g

Area dengan intensitas seismik grade 8:

Ground horizontal acceleration {{0}}.25g,  ground vertical acceleration 0.125g

Area dengan intensitas seismik grade 7:

Percepatan horizontal tanah {{0}}.2g, percepatan vertikal tanah 0,1g

19

Suhu penyimpanan dan transportasi di bawah lingkungan yang ekstrim

-40 degree -+ 80 degree

20

Properti pelindung kandang

Outdoor installation parts (the system and communication control unit) IP56

21

Dimensi batas

lebar 585mm kedalaman425mm tinggi 1010mm

22

Berat keseluruhan

125kg

23

Ukuran dasar

lebar 700mm kedalaman 380mm tinggi300mm

image012

image014

image016

Tag populer: HZGC-1210 Sistem Pemantauan Analisis Gas Terlarut (DGA) Online Untuk Transformator Daya, Cina, pemasok, produsen, harga, untuk dijual, uji analisis gas terlarut minyak transformator, pemantauan dga (analisis gas terlarut) online, sistem pemantauan kromatografi gas online, HZGC-1210, Kromatografi gas online, transformator monitor gas terlarut online